DEUTZ 2300 Kva

Sales Price 200.000 Euro

Technical data 50 HZ


Set Type GTD 2200A

Gen set capacity COP according ISO 8528 kVA 2110

Gen set capacity LTP according ISO 8528 kVA 2200

Power factor Cos j  0.8

Derating for altitude >1000 m %/500 m -

Derating for temperature >+40°C %/10° C -

Heat rejection totally at 100% load kW 275

Weight of dry set excluding radiator kg 13400

Weight of dry radiator kg 1850

Expected wet weight set excluding radiator kg 13740

Engine Make Deutz

Engine Type TBD 620 V16

Engine speed rpm 1500

Engine max net output kW 1936

Engine cylinders pcs 16

Engine cylinder volume litres 70.6

Stability of speed + % 0.5

Fuel consumption 100% load (prime) l/h 460

Fuel consumption 75% load l/h 345

Fuel consumption 50% load l/h 253

Air volume for combustion m3/h -

Air volume for cooling m3/h 100000

Lube oil consumption new engine gr/h -

Alternator Make Stamford

Alternator Type P70L24C

Rated output at class H insulation kVA 2300

Voltage standard V 230/400

Voltage alternatives under heading alternator

Rated current A 3320

Frequency Hz 50

Stability of voltage + % 1

Stability of frequency + % 0.5

Current overload capability in 2 min. % 50

Current overload capability in 10sec. % 300

Technical information

Engine No. TBD 620 V16

Generator No. P70L24C

------------------------------------------

Power standard According international standard ISO 8528

COP Continuous power 100% load at 100% time

PRP Continuous power with variable load

LTP Limited time power maximum 500 hours per year

Rules The gen set conforms with the requirements of

the following:


ISO 3046/1 Diesel engines

ISO 8528-1 Application, ratings and performance

ISO 8528-2 Diesel engines

ISO 8528-3 Alternators

ISO 8528-4 Control panels

ISO 8528-5 Gen sets

ISO 8528-6 Test methods

Norms The set is manufactured according the following norms.

ISO 8528, IEC 34, IEC 364

EC directives Genetech’s sets are delivered in conformity with stated requirements of the

European Council Directives. The sets are clearly CE marked and delivered with EC declaration of conformity.

Testing The set is tested in test room with full load before delivery.

The following tests are done before delivery:

- Mechanical and electrical check

- Electrical function control

- Load test 0-100% and overload capability

A full test report is delivered with the set.

Construction of The single bearing generator is directly flanged to the diesel engine

the set flywheel. The common flanged unit is rubber mounted on

a rigid base frame.

--------------------------------------------------------------------------------------------

Diesel engine Standard industrial 4-stroke type, direct injected, water-cooled type and

equipped with:

- Injector pump with electronic speed regulator

- Electric starter 24 V DC

- Electric stop solenoid 24 V DC

- Engine temp gauge

- Lube oil pressure gauge

- Engine temp switch

- Lube oil pressure switch

- Radiator with electrical driven fan

Lube oil pump For draining of the engine lube oil sump is mounted one lube oil sump

draining pump.

Alternator Brushless synchronous alternator with automatic

electronic controlled voltage regulator.

RFI suppressed according to VDE 0875 grade N.

The alternator is equipped with permanent greased maintenance free ball

bearing.

The alternator is equipped with the following:

- Electronic voltage regulator

- Static unit for parallel operation with mains

Control panel The control panel is designed for automatic operation of stationary fully automatic

standby generators. The capacity is calculated for 230/400 V 50 Hz and the panel

is equipped with the following.

1- Current transformer

1- Overload relay

1- Operation relay

X- Terminals

1- Three-pole circuit breaker

1- Two-pole circuit breaker

1- Charging rectifier

1- Aux relay for charging rectifier

1- Rectifier bridge for charger

1- Pushbutton "Start"

1- Pushbutton "Stop"

1- Pushbutton "Reset/Lamp test"

1- Duty selector "0-Hand-Auto"

1- Pushbutton "Emergency stop"

1- Running hour meter

1- Engine temp instrument

1- Engine lube oil pressure instrument

1- Electronic control system Cisco 2000 for automatic start, stop and

supervision of the set.

The following facility is included.

1- Alarm system with the following indications


Shutdown alarms for the following

-High generator voltage +10%

-Low generator voltage -15%

-High generator frequency +15%

-Low generator frequency -10%

-Over current

-Low engine lube oil pressure

-High engine temp

-Start failure

-Emergency stop

-Low water level

-Reverse power

-Spare channel

-Spare channel

Indicating alarm for following.

-Low battery voltage

-Tripped circuit breaker

-Low fuel level

For status is the following indication available

-Set in operation

-Set on standby

-Generator breaker on

-Mains breaker on

-Mains voltage approved

The control system is also equipped with digital instruments for

visual indication of the following.

1- Digital voltmeter 0-600 V + 1%

1- Ampere meter 0-1999 A + 1%

1- Frequency meter 0-75 Hz + 0,1%

For presentation of the measurements from the gen set is the control system

Equipped with digital instrument for measuring voltage, frequency and current.

The electronic control system consists of 7 electronic Euro boards with plug

in contacts.


The electronic boards is changeable between different types of Genetechs

generating sets independent of the kVA size on the sets.

This means that less spare boards is needed for customers with several sets in

operation. All electronic boards included in the electronic system is made for

operation in ambient temperature between –40 to +65 Celsius and can therefore

also be used in mobile applications.


Fuel tank A standard fuel day tank is included with a volume of 2000 litres.

The fuel day tank is equipped with 600 mm high legs to give static pressure

into the engine fuel suction pump. This day tank is made for automatic

filling from an external storage tank and equipped with the following.

- Fuel filling cap 2”

- Fuel gauge for instrument, start and stop of pump and alarm

- Fuel feeding connection to engine with stop valve

- Fuel return connection from engine with non return valve

- Fuel draining plug with valve and plug

- Manhole for inspection

- Hand pump for manual filling of the tank


Exhaust The set is delivered with the following exhaust equipment.

equipment

1- Silencer type DDA

1- Silencer ADS

1- Flexible exhaust fitting

1- Exhaust pipe in the gen set room

1- Insulation on exhaust system 100 mm with al-cover

1- Exhaust system with insulation to roof level app. 30 metres

X- Support for the exhaust system up to roof level.

The dimensions of the above exhaust system is designed for the

output of the generating set

Ventilation The set is delivered with the following ventilation equipment.

equipment

2- Motor operated ventilation louvres

1- Air discharge duct silencer

1- Fixed grid for air intake from garage

The dimensions of the above ventilation system is designed for the

output of the generating set


Battery Combined battery for start and control of make Tudor type acid lead is

included. The battery is mounted on a battery shelf alongside the base frame.

The battery capacity is calculated for five start attempts of five

seconds with five seconds rest in between.

Labels All labels in English on set and control panels.

Manuals Three maintenance and operation manuals are delivered with the gen set.

The manuals contain the following information:

  1. Starting instructions
  2. Engine handbook
  3. Generator handbook
  4. Circuit diagrams
  5. Component lists
  6. Service journals
  7. Trouble shooting tables.