DEUTZ 2300 Kva
Sales Price 200.000 Euro
Technical data 50 HZ
Set Type GTD 2200A
Gen set capacity COP according ISO 8528 kVA 2110
Gen set capacity LTP according ISO 8528 kVA 2200
Power factor Cos j 0.8
Derating for altitude >1000 m %/500 m -
Derating for temperature >+40°C %/10° C -
Heat rejection totally at 100% load kW 275
Weight of dry set excluding radiator kg 13400
Weight of dry radiator kg 1850
Expected wet weight set excluding radiator kg 13740
Engine Make Deutz
Engine Type TBD 620 V16
Engine speed rpm 1500
Engine max net output kW 1936
Engine cylinders pcs 16
Engine cylinder volume litres 70.6
Stability of speed + % 0.5
Fuel consumption 100% load (prime) l/h 460
Fuel consumption 75% load l/h 345
Fuel consumption 50% load l/h 253
Air volume for combustion m3/h -
Air volume for cooling m3/h 100000
Lube oil consumption new engine gr/h -
Alternator Make Stamford
Alternator Type P70L24C
Rated output at class H insulation kVA 2300
Voltage standard V 230/400
Voltage alternatives under heading alternator
Rated current A 3320
Frequency Hz 50
Stability of voltage + % 1
Stability of frequency + % 0.5
Current overload capability in 2 min. % 50
Current overload capability in 10sec. % 300
Technical information
Engine No. TBD 620 V16
Generator No. P70L24C
------------------------------------------
Power standard According international standard ISO 8528
COP Continuous power 100% load at 100% time
PRP Continuous power with variable load
LTP Limited time power maximum 500 hours per year
Rules The gen set conforms with the requirements of
the following:
ISO 3046/1 Diesel engines
ISO 8528-1 Application, ratings and performance
ISO 8528-2 Diesel engines
ISO 8528-3 Alternators
ISO 8528-4 Control panels
ISO 8528-5 Gen sets
ISO 8528-6 Test methods
Norms The set is manufactured according the following norms.
ISO 8528, IEC 34, IEC 364
EC directives Genetech’s sets are delivered in conformity with stated requirements of the
European Council Directives. The sets are clearly CE marked and delivered with EC declaration of conformity.
Testing The set is tested in test room with full load before delivery.
The following tests are done before delivery:
- Mechanical and electrical check
- Electrical function control
- Load test 0-100% and overload capability
A full test report is delivered with the set.
Construction of The single bearing generator is directly flanged to the diesel engine
the set flywheel. The common flanged unit is rubber mounted on
a rigid base frame.
--------------------------------------------------------------------------------------------
Diesel engine Standard industrial 4-stroke type, direct injected, water-cooled type and
equipped with:
- Injector pump with electronic speed regulator
- Electric starter 24 V DC
- Electric stop solenoid 24 V DC
- Engine temp gauge
- Lube oil pressure gauge
- Engine temp switch
- Lube oil pressure switch
- Radiator with electrical driven fan
Lube oil pump For draining of the engine lube oil sump is mounted one lube oil sump
draining pump.
Alternator Brushless synchronous alternator with automatic
electronic controlled voltage regulator.
RFI suppressed according to VDE 0875 grade N.
The alternator is equipped with permanent greased maintenance free ball
bearing.
The alternator is equipped with the following:
- Electronic voltage regulator
- Static unit for parallel operation with mains
Control panel The control panel is designed for automatic operation of stationary fully automatic
standby generators. The capacity is calculated for 230/400 V 50 Hz and the panel
is equipped with the following.
1- Current transformer
1- Overload relay
1- Operation relay
X- Terminals
1- Three-pole circuit breaker
1- Two-pole circuit breaker
1- Charging rectifier
1- Aux relay for charging rectifier
1- Rectifier bridge for charger
1- Pushbutton "Start"
1- Pushbutton "Stop"
1- Pushbutton "Reset/Lamp test"
1- Duty selector "0-Hand-Auto"
1- Pushbutton "Emergency stop"
1- Running hour meter
1- Engine temp instrument
1- Engine lube oil pressure instrument
1- Electronic control system Cisco 2000 for automatic start, stop and
supervision of the set.
The following facility is included.
1- Alarm system with the following indications
Shutdown alarms for the following
-High generator voltage +10%
-Low generator voltage -15%
-High generator frequency +15%
-Low generator frequency -10%
-Over current
-Low engine lube oil pressure
-High engine temp
-Start failure
-Emergency stop
-Low water level
-Reverse power
-Spare channel
-Spare channel
Indicating alarm for following.
-Low battery voltage
-Tripped circuit breaker
-Low fuel level
For status is the following indication available
-Set in operation
-Set on standby
-Generator breaker on
-Mains breaker on
-Mains voltage approved
The control system is also equipped with digital instruments for
visual indication of the following.
1- Digital voltmeter 0-600 V + 1%
1- Ampere meter 0-1999 A + 1%
1- Frequency meter 0-75 Hz + 0,1%
For presentation of the measurements from the gen set is the control system
Equipped with digital instrument for measuring voltage, frequency and current.
The electronic control system consists of 7 electronic Euro boards with plug
in contacts.
The electronic boards is changeable between different types of Genetechs
generating sets independent of the kVA size on the sets.
This means that less spare boards is needed for customers with several sets in
operation. All electronic boards included in the electronic system is made for
operation in ambient temperature between 40 to +65 Celsius and can therefore
also be used in mobile applications.
Fuel tank A standard fuel day tank is included with a volume of 2000 litres.
The fuel day tank is equipped with 600 mm high legs to give static pressure
into the engine fuel suction pump. This day tank is made for automatic
filling from an external storage tank and equipped with the following.
- Fuel filling cap 2”
- Fuel gauge for instrument, start and stop of pump and alarm
- Fuel feeding connection to engine with stop valve
- Fuel return connection from engine with non return valve
- Fuel draining plug with valve and plug
- Manhole for inspection
- Hand pump for manual filling of the tank
Exhaust The set is delivered with the following exhaust equipment.
equipment
1- Silencer type DDA
1- Silencer ADS
1- Flexible exhaust fitting
1- Exhaust pipe in the gen set room
1- Insulation on exhaust system 100 mm with al-cover
1- Exhaust system with insulation to roof level app. 30 metres
X- Support for the exhaust system up to roof level.
The dimensions of the above exhaust system is designed for the
output of the generating set
Ventilation The set is delivered with the following ventilation equipment.
equipment
2- Motor operated ventilation louvres
1- Air discharge duct silencer
1- Fixed grid for air intake from garage
The dimensions of the above ventilation system is designed for the
output of the generating set
Battery Combined battery for start and control of make Tudor type acid lead is
included. The battery is mounted on a battery shelf alongside the base frame.
The battery capacity is calculated for five start attempts of five
seconds with five seconds rest in between.
Labels All labels in English on set and control panels.
Manuals Three maintenance and operation manuals are delivered with the gen set.
The manuals contain the following information:
- Starting instructions
- Engine handbook
- Generator handbook
- Circuit diagrams
- Component lists
- Service journals
- Trouble shooting tables.